Would you save enough in energy costs to make it worth sealing your air ducts? This industry study can help you find out

by Brianna Crandall — March 16, 2018 — A new study from the nonprofit Center for Energy and Environment (CEE) examining the viability of duct sealing in commercial buildings revealed several criteria that could be used to help identify buildings most likely to realize significant energy- and cost-saving benefits from air duct sealing. The study also concluded that aerosol-based duct sealing proved more effective and produced a faster return on investment (ROI) as compared to traditional duct sealing methods, particularly when access to ductwork was limited.

Highlights of the study, Duct Leakage and Retrofit Duct Sealing in Minnesota Commercial and Institutional Buildings, have been developed into a new infographic: “5 Game-Changing Facts About Air Ducts,” which is available for download on the Aeroseal Web site.

Infographic on duct sealing benefits

The CEE study revealed several criteria that could be used to help identify buildings most likely to realize significant energy- and cost-saving benefits from air duct sealing. Image courtesy CEE/Aeroseal. Click to enlarge.

The study and the infographic will be presented by CEE Senior Research Engineer Josh Quinnell, Ph.D., at a joint Webinar scheduled for March 29, 2018, at 1:30pm EDT. Quinnell pointed out:

Duct leakage can result in a major hit on buildings’ energy use and cause a substantial increase in operating costs. Our study identified key criteria to pinpoint those buildings that are most likely to experience leakage, and consequently benefit the most from duct sealing.

The four criteria that can be helpful in identifying buildings with the biggest potential for energy savings include:

  • System type: Exhaust systems, especially those traversing unconditioned space; supply systems located in ceiling plenum returns; or supply systems with fully ducted returns
  • Operating pressure: Operating pressure of at least 0.5” w.g. are acceptable; above 1.0” w.g. are preferred
  • Design flow: Design flows greater than 4,000 cfm are acceptable; greater than 10,000 cfm are preferred
  • Apparent tightness: Systems with existing sealant and systems of apparently tight construction (i.e. spiral) are less likely to have substantial leakage

The study also found that aerosol-based duct sealing was typically more effective than traditional duct sealing (tape/mastic), especially when the ducts were insulated or access to the entire duct system was limited. Quinnell stated:

Using aeroseal technology, the median sealing rate was 86% and often reduced effectively to zero — among the highest energy conservation rates we’ve studied. Our study predicts an average ROI of around seven years, achieved by first identifying the buildings best suited for sealing and then using the aerosol sealing process to do the work.

For more information on the CEE research project; to view or download the infographic: “5 Game-Changing Facts About Air Ducts;” to register for the Webinar; or for more information about Aeroseal technology, visit the respective Web sites.